FTX-N/U, FVXS-N, FDMQ-R Series
14.16 <KRCS01-4B> Remote Sensor
Notes
•
Please check applicable kit model name by catalog etc.
•
When installed on SkyAir Round-flow type models, the dehumidification by detection of humidity does not operate.
Accessories
Check the following accessories.
Remote sensor
N
a
m
e
(sensor box)
1
Shape
Quantity
Mounting
1) Selection of mounting location.
The thermistor for temperature detection is incorporated into the remote sensor. Select the mounting location taking the
following cautions into account.
1 Where the average temperature of an air conditioned room can be detected.
2 Where it is not exposed to the direct sunlight.
3 Where it is not influenced by other heat sources.
4 Where it is not exposed to the direct discharge air from the air conditioner.
5 Where it is not exposed to the outdoor air infiltrated into the room by opening the door.
2) Mounting
•
Remove the cover of the sensor box.
about 6mm width
flat blade screw driver
Extension cable
(2-core, 12m)
2
3
x 1
x 1
1 Insert a flat blade screw driver into the sensor box concave part (2 locations).
2 Remove the cover pushing up the nail to the cover of the sensor box.
2
<Cautions>
Do not push the nail powerfully with a narrow flat blade screw driver,
1
because you may break off the nail.
Installation
Mounting screw
manual