FTX-N/U, FVXS-N, FDMQ-R Series
2. BEFORE INSTALLATION
When unpacking the indoor unit or moving the unit after
unpacked, hold the hangers (4 places) and do not apply
force to other parts (particularly refrigerant piping, drain
piping).
• For installation of the outdoor unit, refer to the installation
manual attached to the outdoor unit.
• Do not throw away the accessories until the installation work
is completed.
• After the indoor unit is carried into the room, to avoid the
indoor unit from getting damaged, take measures to protect
the indoor unit with packing materials.
(1) Determine the route to carry the unit into the room.
(2) Do not unpack the unit until it is carried to the
installation location.
Where unpacking is unavoidable, use a sling of soft
material or protective plates together with a rope when
lifting, to avoid damage or scratches to the indoor unit.
• Have the user actually operate the air conditioner while
looking at the operation manual.
Instruct the user how to operate the air conditioner
(particularly operation pro cedures, and temperature
adjustment).
• Do not use the air conditioner in a salty atmosphere such as
coastal areas, vehicles, vessels or where voltage fluctuation
is frequent such as factories.
• Take off static electricity from the body when carrying out
wiring and the electrical wiring box cover is removed.
The electric parts may be damaged.
2-1 ACCESSORIES
(1) Clamp
Name
metal
Quantity
1
Shape
Fitting
Name
insulation
Quantity
1 each
Thin
(4) For liquid
pipe
Shape
Thick
(5) For gas
pipe
(9) W asher fixing
Name
plate
Quantity
4
Shape
Name
(12) Conduit mounting plate
Quantity
Shape
3
01_EN_3P500432-1.indd 3
(3) D uct flange connection
(2) Drain
screw
hose
09/12 class
15/18/24 class
1
10
18
(6) Sealing
(7) Sealing
(8) Clamp
pad
pad
1
2
8
Medium
Large
(Dark gray)
(Dark gray)
(10) Wire sealing
(11) Washer for
pad
hanger bracket
2
8
Small
(Gray)
Others
1
• Operation manual
• Installation manual
• Warranty
2-2 OPTIONAL ACCESSORIES
• A remote controller is required for the indoor unit.
• Select a remote controller from the table below according to
user request and install in an appropriate place.
Remote controller type
Wired type
Wireless type
• The indoor unit can be switched to lower suction.
(Refer to 4. PREPARATION BEFORE INSTALLATION.)
The side cover plate (KDBD63A160) is required in the case
of wiring from the bottom for underside suction.
For installation work, refer to the instruction sheet provided
with the side cover plate.
CARRY OUT THE WORK GIVING CAUTION
TO THE FOLLOWING ITEMS AND AFTER THE
WORK IS COMPLETED CHECK THESE AGAIN.
Items to be checked after the installation work is
1.
completed
Items to be checked
Are the indoor and outdoor
Drop · vibration ·
units rigidly fixed?
noise
Are the installation works of
Does not operate ·
the outdoor and indoor units
burnout
completed?
Is the insulation of refrigerant
piping and drain piping
Water leakage
completely carried out?
Does the drain flow out
Water leakage
smoothly?
Is the power supply voltage
identical to that stated in the
Does not operate ·
manufacturer's label on the
burnout
air conditioner?
Are you sure that there is no
Does not operate ·
wrong wiring or piping or no
burnout
loose wiring?
Danger in case of
Is grounding completed?
leakage
Are the sizes of electric
Does not operate ·
wiring according to the
burnout
specification?
Are any of air outlets or inlets
of the indoor and outdoor
units blocked with obstacles?
Does not cool /
(It may lead to capacity drop
Does not heat
due to fan speed drop or
malfunction of equipment.)
Is the external static
Does not cool /
pressure set correctly?
Does not heat
Also review the "SAFETY CONSIDERATIONS".
112
EDUS091558E
BRC1E73
BRC082A43