Short Circuit Protection Requirements For Ul Listing - YASKAWA FP605 Installation & Primary Operation

Ac drive for industrial fan and pump applications
Hide thumbs Also See for FP605:
Table of Contents

Advertisement

Model
Terminals
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4302
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4361
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4414
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4477
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4515
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4590
-, +1
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
4720
-, +1
*1
Use recommended ferrule or bare wire.
*2
The recommended wire gauge for this part is AWG 2.

Short Circuit Protection Requirements for UL Listing

WARNING
Electrical Shock Hazard. After the input protective device trips, do not immediately energize the drive or operate
peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators are OFF. Then
check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of the problem, contact
Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you operate the drive or peripheral
devices, it can cause serious injury or death.
YASKAWA TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION
Recommended
Gauge
*1
Ferrule
AWG, kcmil
3/0 × 2
N/A
3/0 × 2
N/A
4/0 × 2
N/A
1/0
N/A
4/0 × 2
N/A
4/0 × 2
N/A
300 × 2
N/A
1/0
N/A
250 × 2
N/A
300 × 2
N/A
350 × 2
N/A
1/0
N/A
3/0 × 4
N/A
3/0 × 4
N/A
4/0 × 4
N/A
2/0
N/A
4/0 × 4
N/A
4/0 × 4
N/A
250 × 4
N/A
2/0
N/A
4/0 × 4
N/A
250 × 4
N/A
300 × 4
N/A
3/0
N/A
300 × 4
N/A
300 × 4
N/A
400 × 4
N/A
4/0
N/A
Crimp Terminal Part Number
Manufacturer: PANDUIT Corp.
Type LCA
Type P
LCA3/0-12-X
N/A
LCA3/0-12-X
N/A
LCA4/0-12-X
N/A
LCA1/0-12-X
N/A
LCA4/0-12-X
N/A
LCA4/0-12-X
N/A
LCA300-12-X
N/A
LCA1/0-12-X
N/A
LCA250-12-X
N/A
LCA300-12-X
N/A
LCA350-12-X
N/A
LCA1/0-12-X
N/A
LCA3/0-12-X
N/A
LCA3/0-12-X
N/A
LCA4/0-12-X
N/A
LCA2/0-12-X
N/A
LCA4/0-12-X
N/A
LCA4/0-12-X
N/A
LCA250-12-X
N/A
LCA2/0-12-X
N/A
LCA4/0-12-X
N/A
LCA250-12-X
N/A
LCA300-12-X
N/A
LCA3/0-12-X
N/A
LCA300-12-X
N/A
LCA300-12-X
N/A
LCA400-12-6
N/A
LCA4/0-12-X
N/A
12 UL Standards
Type S
S3/0-76R-5
or
S3/0-12R-5
S3/0-76R-5
or
S3/0-12R-5
S4/0-76R-5
or
S4/0-12R-5
S1/0-12R-X
S4/0-12R-5
S4/0-12R-5
N/A
S1/0-12R-X
S250-12R-5
N/A
N/A
S1/0-12R-X
S3/0-12R-5
S3/0-12R-5
S4/0-12R-5
S2/0-12R-X
S4/0-12R-5
S4/0-12R-5
S250-12R-5
S2/0-12R-X
S4/0-12R-5
S250-12R-5
N/A
S3/0-12R-5
N/A
N/A
N/A
S4/0-12R-5
79

Advertisement

Table of Contents
loading