Programming Cautions
14.1 Programming Cautions
14.1.1 Turning Off Power Supply Clears Contents of Unit Memory
The unit memory data of the positioning unit will be cleared when the PLC is turned off.
14.1.2 Not Going to Other Operation from Current Operation
Automatic operation (positioning control) or manual operation (JOG operation, home return, or
pulser operation) that has started with the start contact turned ON will continue even if the
contact of other operation turns ON.
However, the stop operation (deceleration stop, emergency stop, system stop) can be
executed during other types of operation.
14.1.3 Operation with the PLC Set to PROG. Mode from RUN Mode
Automatic operation (positioning control) or manual operation (JOG operation, home return, or
pulser operation) that has started with the start contact turned ON will continue even if the
PLC is switched to PROG. mode from RUN mode.