11.02
Remedy:
Program Continuation:
27253
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
27254
Parameters:
Definitions:
Reactions:
Remedy:
Program Continuation:
27255
Parameters:
Definitions:
 Siemens AG, 2002. All rights reserved
SINUMERIK 840D/840Di/810D Diagnostics Guide (DA) – 11.02 Edition
Restart F slave modules. Restart the NCK/PLC.
Clear alarm with the RESET key. Restart part program
PROFIsafe: communication fault F master component %1, error %2
%1 = Error component (NCK/PLC)
%2 = Error code
The F master signals that the communication between the NCK and PLC is no longer
working.
The error code %1 specifies the cause:
• %1 = NCK: Link between PROFIsafe and SPL interface is interrupted.
• %1 = PLC: the PLC does no longer execute the OB40 request.
• %1 = PLC-DPM: DP master is no longer in OPERATE status.
Parameter %2 provides further information about the error's cause:
• %2 = 0: NCK-internal sequence error (see %1=NCK).
• %2 = 1,2,4: PLC processing of the OB40 not finished.
- Mode group not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Extend the PROFIsafe cycle time via MD $MN_PROFISAFE_IPO_TIME_RATIO.
Clear alarm with the RESET key. Restart part program
PROFIsafe: F module %1, error on channel %2; %3<ALSI>
%1 = PROFIsafe address
%2 = Channel number
%3 = System variable array index extension
The F module signals that an error occurred in the interface of the specified channel.
This alarm is only triggered for ET200S F modules.
%2=0: Special meaning: A general error occurred in the F module.
A specific alarm message can be programmed for each of the system variables on the
MMC via parameter %3:
• %3 = 1....64: Error in system variables $A_INSE[1...64]
• %3 = 65...128: Error in system variables $A_OUTSE[1...64]
- Mode group not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
Check wiring. Wiring OK: replace F module.
Clear alarm with the RESET key. Restart part program
PROFIsafe: F module %1, general error
%1 = PROFIsafe address
The specified PROFIsafe module signals an error. A more exact specification of the
error's cause cannot be made without further assistance.
This alarm is triggered for all types of PROFIsafe slaves.
With ET200S F modules, this error can only occur if there already is a channel error when
the cyclical communication between the F master and module is begun.
1 Alarms
1-369