Installing the S8700 Multi-Connect
Installing an Avaya MCC1 Media Gateway

Install Coupled Bonding Conductor Wires

This is a conductor that connects to the single-point ground block and runs adjacent to pairs in
an associated cable. The mutual coupling between the CBC and the pairs reduces potential
differences in terminating equipment. The conductor consists of a 10 AWG (#25) (6 mm
terminated at the CBC ground terminal bar at the Main Distribution Frame (MDF).
1
2
3
NOTE:
The ground wires are connected to the CBC as instructed in
page
Connect Grounds for DC Battery and Power
Cabinets
NOTE:
The wire in the next step must be sized for a maximum voltage drop of 0.5 VDC in each
leg of the DC distribution. In this example 1 AWG is used.
1
2
3
4

Connect DC Power cabinet Approved Ground

NOTE:
The wire must be at least as large as the largest distribution wire in the S8700
Multi-Connect configuration (required by UL). In this example 1 AWG is used.
1
2
At the DC power cabinet, connect a 10 AWG (#25) (6 mm
Discharge Bar. See
''Typical Power and Ground for a DC power cabinet'' on page
Route the 10 AWG (#25) (6 mm
MDF. Be sure a minimum of 12 in. (30.5 cm) spacing is maintained between the CBC
and other power and ground leads.
Tie wrap the ground wire to the inside wiring cable.
116.
Measure and cut a minimum of a 1 AWG (#70) (44 mm
between the ground connection terminal in the DC Battery cabinet and the Ground
Discharge Bar in the DC Power cabinet. See
power cabinet'' on page
Crimp terminal lugs on each end of the wire. Terminal lugs are furnished as part of
D-181895, Kit of Parts (Comcode 105434559).
At the DC power cabinet, connect the wire to the Ground Discharge Bar.
Route the wire through one of the holes in the side of the cabinets and terminate it on the
Ground Connection Terminal in the DC battery cabinet.
At the DC power cabinet, connect a 1 AWG (#70) (44 mm
Discharge Bar. See
''Typical Power and Ground for a DC power cabinet'' on page
Route the ground wire out of the cabinet and terminate it on the approved ground. The
approved ground must be identified with a grounding tag (FORM 15657NR or
equivalent). See
Approved
2
) ground wire to the CBC ground terminal bar at the
''Typical Power and Ground for a DC
60.
Grounds.
May 2002
2
) ground wire to the Ground
''Cabling Port Networks'' on
2
) wire long enough to reach
2
) ground wire to the Ground
2
) wire
60.