Installing the S8700 Multi-Connect
Installing an Avaya MCC1 Media Gateway

Connect Power and Ground(s)

Have a qualified electrician connect and route wires from the AC load center to the dedicated
electrical outlet for the power distribution unit.
1
2
3
Power Distribution Unit (J58890CH)
pcdf010 KLC 020599
Figure notes
1
2
3
4
5
6
7
8
Connect 1 end of a 6 AWG (#40) (16 mm
terminal block at the bottom rear of the cabinet. See
Wiring Diagram'' on page
Route the cabinet GROUND wire to the AC load center single-point ground and connect.
Connect each remaining media gateway to the AC load center single-point ground.
Connect small battery holdover cable (or temperature sensor cable from large battery
cabinet) to J20
Carrier Circuit Breakers
Ground Terminal Block
Connect -48 VDC Return - 1 AWG (50 mm
Connect -48 VDC - 1 AWG (50 mm
2
1 AWG (50 mm
) 50 ft. (15.2 m) cable to large battery cabinet. For cables greater than 50
ft. (15.2 m), contact your Avaya representative.
Ground Terminal Block
To AC load center or approved single-point ground block
2
) cabinet GROUND wire to the ground
63.
1
5
6
2
) red cable here.
2
) black cable
May 2002
''Typical Media Gateway Grounding
2
3
7
4
8