Avaya S8700 Installing Manual page 34

For multi-connnect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

34
Installing the S8700 Multi-Connect
Configure the Hardware in the Rack
3
4
5
6
7
8
9
NOTE:
If the UPS units are going to be monitored by a Network Management System (NMS)
coordinate the assignment of the community names with the local LAN administrator. See
the Pre-Installation Network Worksheet for S8700 Multi-Connect. If a NMS will not
monitor the UPS units set the community names to unique string values.
10
NOTE:
The Host Table should be empty. If not, in the following commands use a host table entry
that is currently unassigned.
11
12
13
14
15
16
17
18
Administer the emulation program port settings:
9600 baud rate
No parity
8 bits
1 stop bit
Press
The Main Configuration screen appears. If the Main Configuration screen
Enter.
does not appear, Press
Enter.
Type BR 0 and press
Enter.
Type IP 198.152.254.239 and press
Type NM 255.255.255.0 and press
Type GW 198.152.254.201 and press
If supplied enter the Get and Set community names with the following commands:
Type CG name and press
alphanumeric characters for the name. The name field is case sensitive and cannot
contain blanks.)
Type CS name and press
alphanumeric characters for the name. The name field is case sensitive and cannot
contain blanks.)
Type HS and press
Enter.
Type HI1 aaa.bbb.ccc.ddd and press
Type TL1 3 and press
Enter.
Type TT1 1and press
Enter.
Type HS and press
Enter.
Type CF and press
Enter.
Type SA and press
Enter.
When completed, disconnect the services laptop computer from the UPS.
Connect a CAT5 cable to the RJ45 connector on the UPS SNMP module and to the next
available port on the Cajun Ethernet switch for Control Network A.
again.
(Sets the BOOTP retry counter to zero.)
(Default IP Address for this UPS)
Enter.
(Default subnet mask for this UPS)
Enter.
(Default gateway for this UPS)
Enter.
(Enters the Get community name. Type up to 16
Enter.
(Enters the Set community name. Type up to 16
Enter.
(Displays the Host Table)
(Sets the trap destination for this UPS).
Enter.
(Sets the trap level for the host, All traps)
(Sets the trap type, Standard UPS MIB-defined)
Verify the table entries. (re-displays the host table)
(re-displays the basic administration screen)
(Saves configuration and restarts module)
May 2002