Connect Dc Power Cabinet Ground - Avaya S8700 Installing Manual

For multi-connnect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

86
Installing the S8700 Multi-Connect
Installing an Avaya SCC1 Media Gateway Stack
Ground for the DC-Powered Distribution Unit
Figure notes
1
2
3
4
5
6

Connect DC Power Cabinet Ground

1
2
3
4
j58890r1 RBP 042296
DC power cabinet
DC Power Distribution Unit
Ground Discharge Bar
6 AWG (#40) (4 mm2) Wire
GRD Connector Terminal on DC-Powered Distribution Unit
To Additional DC-Powered Distribution Units (if required)
Cut a length of 6 AWG (#40) (4 mm
DISCHARGE bar on the DC power cabinet and the single-point ground block on the
expansion control media gateway A (bottom media gateway in
Gateway'' on page
87).
At the DC power cabinet, connect the wire to the GROUND DISCHARGE bar.
Route the wire to expansion control media gateway A and connect to the single-point
ground block.
Repeat for each expansion control media gateway A in the S8700 Multi-Connect
configuration room.
2
) wire long enough to reach between the GROUND
May 2002
''Ground for Media