Installing the S8700 Multi-Connect
Installing an Avaya MCC1 Media Gateway
Ground AC Load Center 50 ft. (15.2 m) or Less
from Media Gateway
1
2
3
4
NOTE:
If the media gateway is located remotely (in a separate room or building), connect the
media gateway GROUND wire to an approved ground.
5
6
At the bottom rear of the first media gateway, connect a 6 AWG (#40) (16 mm
gateway GROUND wire to the media gateway ground terminal block. See
Media Gateway Ground Location'' on page
Route the media gateway GROUND wire to the single-point ground block at the AC load
center and connect.
At the bottom rear of the next media gateway (if provided), connect a 6 AWG (#40) (16
2
mm
) media gateway GROUND wire to the media gateway ground terminal block.
Route the media gateway GROUND wire to the single-point ground block at the AC load
center and connect.
Repeat connecting each media gateway to the single-point ground block.
At the AC load center, connect a 10 AWG (#25) (6 mm
block. This ground wire will later be tie-wrapped to the trunk cables and connected to the
Coupled Bonding Conductor (CBC) ground block at the MDF.
The Coupled Bonding Conductor (CBC) wires are installed and terminated in
Port Networks'' on page
53.
116.
May 2002
''Typical
2
) wire to the single-point ground
2
) media
''Cabling