PROFIBUS-PA Status Byte
D.3
Condensed-mode status byte format
Table D-7 describes the format of the status byte when the transmitter is configured for condensed
mode. Refer to the PROFIBUS Specification Profile for Process Control Devices Version v3.01
December 2004 and the PROFIBUS Specification June 2005 Amendment 2 to the PROFIBUS Profile
for Process Control Devices v3.01, Condensed Status and Diagnostic Messages v1.0 for additional
information.
Table D-7
Condensed-mode status byte format
Expanded status
BAD_DEVICE_FAIL (0x0C)
BAD_SENSOR_FAIL (0x10)
BAD_CFG_ERROR (0x04)
BAD_NON_SPECIFIC (0x00)
UC_SIMULATED_VALUE (0x60)
UC_SENSOR_CAL (0x64)
UC_CFG_ERROR (0x5C)
UC_NON_SPECIFIC (0x40)
GOOD_NC_ADV_ALARM (0x88)
GOOD_NC_UPDATE_EVT (0x84)
GOOD_CAS_OK (0xC0)
BAD_OUT_OF_SERVICE |
LIMIT_CONSTANT (0x1C)
Totalizer Fail Safe: UC_NON_SPECIFIC
(0x40)
Totalizer Fail Safe: UC_LUV (0x44)
Configuration and Use Manual
Condensed status
C_BAD_MAINTENANCE_ALARM
(1)(2)
(0x24.....0x27)
C_BAD_PROCESS_RELATED (0x2B)
C_BAD_FUNCTION_CHECK (0x3C
(1)(2)
......0x3F)
BAD_NON_SPECIFIC (0x00)
C_UNCERTAIN_SIMULATED_VALUE_STA
RT (0x73)
C_BAD_FUNCTION_CHECK (0x3C
(1)(2)
......0x3F)
C_BAD_FUNCTION_CHECK
(1)(2)
(0x3C......0x3F)
C_UNCERTAIN_PROCESS_RELATED
(1)
(0x78.. ...0x7B)
C_GOOD_ACTIVE_ADVISORY_ALARM
(1)
(0x88.....0x91)
C_GOOD_UPDATE_EVENT (0x84)
C_GOOD_CAS_OK (0xC0)
C_BAD_PASSIVATED (0x23)
C_UNCERTAINC_SUBSTITUTE_SET
(0x4B)
C_UNCERTAINC_PROCESS_RELATED
(1)
(0x78....0x7B)
Alarms
A001, A002,
A014, A029,
A030
(2)
A003, A004,
A016, A017
A006, A020,
A021
All remaining
fault alarms
under this
category.
A132
A104
A006, A020,
A021
A005, A008,
A010, A011,
A012, A013,
A033, A102
All informational
alarms.
ST revision
update for
transducer
blocks.
None of the
alarms stated
above are active.
Actual mode of
AI, AO, or
totalizer blocks is
Out of Service.
Failsafe – RUN
mode
Failsafe –
HOLD_LUV
mode
139