Configuring The Display; Enabling And Disabling Display Functions - Emerson Micro Motion 2700 Configuration And Use Manual

With profibus-pa
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

Configuration
4.16

Configuring the display

You can restrict the display functionality or change the variables that are shown on the display.
4.16.1

Enabling and disabling display functions

Each display function and its associated parameter are listed in Table 4-16.
Table 4-16
Display functions and parameters
Display function
EDD name
Totalizer reset
Totalizer Reset
Start/stop totalizers
Start/Stop Totalizer
(1)
Auto scroll
Auto Scroll
Off-line menu
Offline Menu
(2)
Off-line password
Offline Password
Alarm menu
Alarm Menu
Acknowledge all
ACK All Alarms
alarms
Display backlight
Backlight
(1) If enabled, you may want to configure Scroll Rate. See Section 4.16.2.
(2) If enabled, the display offline password must also be configured. See Section 4.16.4.
Note the following:
If you use the display to disable access to the off-line menu, the off-line menu will disappear
as soon as you exit the menu system. If you want to re-enable access, you must use a different
method (e.g., ProLink II).
If you are using the display to configure the display:
-
You must enable Auto Scroll before you can configure Scroll Rate.
-
You must enable the off-line password before you can configure the password.
To enable or disable display functions:
With the EDD, refer to Figure 4-17.
With bus parameters, refer to Figure 4-18.
With ProLink II, refer to Figure 4-19.
With the display, refer to Figure B-13.
Configuration and Use Manual
Display
code
Enabled
TOTALS
Resetting mass and
RESET
volume totalizers is
permitted.
TOTALS
Operator can start and
STOP
stop totalizers from the
display.
AUTO
The display automatically
SCRLL
scrolls through each
process variable.
DISPLAY
Operators have access to
OFFLN
the off-line menu.
OFFLINE
Password required for
PASSW
offline menu. See
Section 4.16.4.
DISPLAY
Operator has access to
ALARM
alarm menu.
DISPLAY
Operator can
ACK
acknowledge all current
alarms at once.
DISPLAY
Display backlight is ON.
BKLT
Disabled
Resetting mass and
volume totalizers is not
possible.
Operator cannot start or
stop totalizers from the
display.
Operators must Scroll to
view process variables.
No access to the offline
menu.
Offline menu accessible
without a password.
No access to the alarm
menu.
Alarms must be
acknowledged individually.
Display backlight is OFF.
75