Model 2700 PROFIBUS Block Parameters
Table F-5
Transducer block 1 parameters (continued)
Index
Parameter Mnemonic
231
UI_NumDecimals
232
UI_ProcessVariables
(LDO_VAR_1_CODE)
(DD Name: Display Variable 1)
Configuration and Use Manual
Definition
Message
Type
For Totals, the number of digits to
VARIABLE
the right of the decimal point to
display on LDO
Display the Variable
ENUM
#1associated with the code on
the LDO
Data Type/
Size
Store
Default
Access
Structure
/Rate
Value
(HZ)
Unsigned8
1
S
-
R/W
Unsigned16
2
S
0
R/W
Enumerated List of
Modbus
Values / Range
Register /
Coil
78= Not used
79= Not used
80= Not used
81= Not used
82= Not used
83= Not used
84= Not used
85= Not used
86= Not used
87= Not used
88= Not used
89= Not used
90= Not used
91= Not used
92= Not used
93= Not used
94= Not used
95= Not used
96= Not used
97= Not used
98= Not used
99= Not used
100= Not used
101= Not used
102= Not used
103= Not used
104= Not used
105-252 = Not used
253= Not used
254= Not used
255= Not used
0 to 5
R-1368
0 = Mass Flow Rate
R-1117
1 = Temperature
2 = Mass Total
3 = Density
4 = Mass Inventory
5 = Volume Flow
Rate
6 = Volume Total
7 = Volume Inventory
8 – 11 = Not used
12= Not used
13= Not used
14= Not used
15 = API: Corr
Density
16 = API: Corr Vol
Flow
17 = API: Corr Vol
Total
18 = API: Corr Vol Inv
19 = API: Avg
Density
20 = API: Avg Temp
21 = CM: Density At
Ref
22 = CM: Density (
SGU)
23 = CM: Std Vol
Flow Rate
24 = CM: Std Vol
Total
25 = CM: Std Vol
Inventory
26 = CM: Net Mass
Flow
27 = CM: Net Mass
Total
28 = CM: Net Mass
Inv
29 = CM: Net Vol
Flow Rate
30 = CM: Net Vol
Total
31 = CM: Net Vol
Inventory
32 = CM:
Concentration
33 = API: CTL
34-45 = Not used
46 = Raw Tube
Frequency
47 = Drive Gain
48 = Case
Temperature
49 = LPO Amplitude
50 = RPO Amplitude
167