Totalizer Block Parameters - Emerson Micro Motion 2700 Configuration And Use Manual

With profibus-pa
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

Model 2700 PROFIBUS Block Parameters
Table F-17
AO function block views
17
ST_REV
18
TAG_DESC
19
STRATEGY
20
ALERT_KEY
21
TARGET_MODE
22
MODE_BLK
23
ALARM_SUM
Overall sum of bytes in View Object
OD
Parameter Mnemonic
Index
Standard Parameters
28
READBACK
47
POS_D
49
CHECK_BACK
61
Overall sum of bytes in View Object
(+ 13 Standard parameters bytes)
F.4.13

Totalizer block parameters

Table F-18 lists the parameters for the totalizer blocks.
Table F-18
Totalizer block parameters
Index
Parameter Mnemonic
Standard PA parameters
16
BLOCK_OBJECT
17
ST_REV
18
TAG_DESC
19
STRATEGY
20
ALERT_KEY
21
TARGET_MODE
22
MODE_BLK
23
ALARM_SUM
24
BATCH
Configuration and Use Manual
Definition
Message
Type
This object contains the
RECORD
characteristics of the block
A block has static block
SIMPLE
parameters that are not
changed by the process.
Values are assigned to this
parameter during the
configuration of optimization.
The value of ST_REV
increases by 1 after every
change of a static block
parameter.
Every block can be assigned
SIMPLE
a textual TAG description.
The TAG_DESC must be
unambiguous and unique in
the field bus system.
Grouping of function block.
SIMPLE
The STRATEGY field can be
used to group blocks.
This parameter contains the
SIMPLE
identification number of the
plant unit.
This parameter contains
SIMPLE
desired mode normally set by
a control application of an
operator. The modes are
valid alternatively only, i.e.
only one mode can be set at
one time. A write access to
this parameter with more than
one mode is out of the range
of the parameter and has to
be rejected.
This parameter contains the
RECORD
current mode and the
permitted and normal mode
of the block.
This parameter contains the
RECORD
current states of the block
alarms.
This parameter is intended to
RECORD
be used in Batch applications
in line with IEC 61512 Part 1.
Only Function Blocks carry
this parameter. There is no
algorithm necessary within a
Function Block.
2
3
8
13
View 1
View 2
5
2
3
10+13
Data Type/
Size
Store
Default
Access
Structure
/Rate
Value
(HZ)
DS-32
20
S
----
R
Unsigned16
2
N
0
R
OCTET
32
S
' '
R/W
STRING
Unsigned16
2
S
0
R/W
Unsigned8
1
S
0
R/W
Unsigned8
1
S
Auto
R/W
(0x08)
---
DS-37
3
D
R
DS-42
8
D
0,0,0,
R
0
DS-67
10
S
0,0,0,
RW
0
View 3
View 4
Enumerated List of
Modbus
Values / Range
Register /
Coil
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
0x08 – Auto
R-2287
0x10 – Manual
0x80 – OOS
NA
R-2288
NA
NA
NA
NA
185