Emerson Micro Motion 2700 Configuration And Use Manual page 66

With profibus-pa
Hide thumbs Also See for Micro Motion 2700:
Table of Contents

Advertisement

Configuration
Figure 4-4
Setting the petroleum measurement table type
EDD
MMI Coriolis Flow >
Transducer Block >
API
API2540 CTL Table Type
Setting the reference temperature
For the temperature value to be used in CTL calculation, you can use the temperature data from the
sensor, or you can configure external temperature compensation to use temperature data from an
external temperature device.
To use temperature data from the sensor, no action is required.
To configure external temperature compensation, see Section 2.8.
Setting the thermal expansion coefficient
If the CTL derivation method for the petroleum measurement table type is method 2, you need to set
the thermal expansion coefficient (TEC). To set a user-defined TEC, refer to the flowcharts in
Figure 4-5.
Figure 4-5
Setting a user-defined TEC
MMI Coriolis Flow >
Transducer Block >
API
API Thermal Expansion
58
EDD
Coeff
Bus parameters
Table type
ProLink II
ProLink >
Configuration
API Setup tab
Bus parameters
TEC
ProLink II
ProLink >
Configuration
API Setup tab
Block: Transducer Block 2 (Slot 12)
Index 40 (API2540 CTL table type)
Select table type from the
API Table Type
list
Apply
Block: Transducer Block 2 (Slot 12)
Index 39 (API thermal expansion coeff.)
Enter a coefficient in the
User defined TEC box
Apply
Model 2700 Transmitter with PROFIBUS-PA