Switching to Sensor Bus
Mode
By using the Sensor Bus method in DeltaV or applicable Fieldbus host the
user is automatically setting the transmitter in "Out Of Service" mode. Then it
sets the transmitter in the Sensor Bus Mode.

Basic connection and configuration description

1. Make the electrical connection, as described in Figure 4-11, Figure 4-12,
Figure 4-13, and Figure 4-14.
2. Open Radar Master and change protocol to Modbus and modem type to
RS-485.
3. Search for a new online device by selecting New Device in the Device
menu. The default unit has Modbus address 246.
4. Enter the configuration windows as required for the configuration
NOTE
Do not enter any 2210 Display Unit configuration windows.
5. Disconnect from the device.
6. Use the Online Help in the Radar Master for further instructions of how to
configure the transmitter.

Detailed Connection and Configuration description

1. Make the electrical connection, as described in Figure 4-11, Figure 4-12,
Figure 4-13, and Figure 4-14.
2. When you start Radar Master you will get a 'RRM Startup' window with
some options, press Cancel. Go to: Open View\Communication
Preferences\ and set the communication as below:
Disable the HART communication before Enabling the Modbus
Communication (Only necessary if the same Communication Port is
used).
Modem: RS-485
Baud Rate: 4800
Stop bit: 1
Handshake: RTS/CTS/DTR/DSR
Retries: 10
The rest are left as default