3.2.3 Input and output specifications
Input specifications
Item
Insulation method
Rated input voltage
Operating voltage range
Rated input current
Input points per common
Min. on voltage/Min. on current
Max. off voltage/Max. off current
Input impedance
Response time
Operating mode indicator
EN61131-2Applicable type
Circuit diagram
Relay output specifications
Item
Insulation method
Output type
Rated control capacity
Output points per common
Response time
Lifetime
Surge absorber
Operating mode indicator
Note) Resistance load
Circuit diagram
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Optical coupler
24 V DC
21.6 to 26.4 V DC
Approx. 4.3 mA
8 points/common
(Either the positive or negative of input power supply can be
connected to common terminal.)
19.2 V DC/3 mA
2.4 V DC/1 mA
Approx. 5.6 kΩ
off→on
0.6 ms or less
on→off
0.6 ms or less
LED display
TYPE3 (however, according to the above specifications)
Relay insulation
1a output (Relay cannot be replaced.)
Note)
2 A 250 V AC, 2 A 30 V DC
(6 A or less/common)
1 point/common,
3 points/common
off→on
Approx. 10 ms
on→off
Approx. 8 ms
Mechanical
20 million times or more (Frequency of switching: 180 times/min.)
100 thousand times or more (Frequency of switching at the rated
Electrical
control capacity: 20 times/min.)
None
LED display
Description
E16
: R1=5.6 kΩ
R2=1 kΩ
Description
E16/E14
E30
16 points/common
E30
(8 A or less/common)
1 point/common,
4 points/common

Hide quick links: