Panasonic AFPX-C30R User Manual page 173

Fp-x series
Hide thumbs Also See for AFPX-C30R:
Table of Contents

Advertisement

1:1 communication with FP Series PLC
Overview
Connect the FP-X and another FP series PLC using the RS232C interface and the MEWTOCOL-COM
communication protocol.
Note: The MEWTOCOL master function of computer link is recommended as it is easy to
communicate.
• When the data area read command "%01#RDD00000 00001**
values of the data register of the PLC connected to the system are sent as a response. For example, if
the value K100 is stored in DT0 and the value K200 is stored in DT1 of the PLC,
"%01$RD6400C8006F
returned (○○ is the error code).
• In addition to data area read and write commands, MEWTOCOL-COM also provides contact area read
and write as well as many other commands.
System register settings of FP series PLCs (FP0 side)
In the default settings, the COM port is set not to be used. For 1:1 general-purpose serial communication,
the system registers should be set as shown below.
Communication format settings for FP series PLC (FP0 side)
No.
No. 412
Selection of communication mode for COM port
No. 413
Communication format for COM port
No. 414
Baud rate setting for COM port
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
" is sent as a response to the command. If there is an error, "%01!○○**
C
R
Name
" is sent from the FP-X side, the
C
R
Set Value
Computer link
Data length: ......
Parity check: .....
Stop bit: ............
Terminator: ........
Header: ............
Note) These settings should be the
same as the settings of the
connected FP-X.
19200 bps
" is
C
R
8 bits
Odd
1 bit
CR
STX not exist