Precautions on programming
Address
R911C
Control flag
(CH0)
R911D
Control flag
(CH1)
Note:
• The above flags vary during scanning.
Example: If the above flags are used for more than one time as input conditions, there may be the
different states in the same scan. Replace with internal relays at the beginning of the program as a
measure.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Flag conditions
Turns on during execution of pulse output
instructions and then maintains that state
during pulse output from CH0. This flag is
the same for instructions F166 to F175.
Turns on during execution of pulse output
instructions and then maintains that state
during pulse output from CH0. This flag is
the same for instructions F166 to F175.
The uses of the flag in the program
Use this to prohibit the simultaneous
execution of other high-speed counter
instructions and pulse output
instructions, and to verify completion
of an action.
Use this to prohibit the simultaneous
execution of other high-speed counter
instructions and pulse output
instructions, and to verify completion
of an action.