- Setting of FP-X
1) FP-X System register setting
No. 412: Computer link mode
2) Setting of AFPX-COM5
Item
Communication protocol
Action mode
Communication mode
Source port No.
Time out
UDP/IP can be used for the communication method.
In that case, change the setting for [PLC Type Setting] of the GV to [FP series (Ethernet UDP/IP)].
Set the communication protocol of the AFP-COM5 to UDP, and set the send type to UNICAST.
Note:
For the Ethernet communication with the GV, the computer link is used. The GV is the master and the
FP-X is the slave. It cannot be used if setting the FP-X as the master. Note that the unit numbers for the
GV and FP-X are not duplicated.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Setting value
TCP
Server mode
Computer link
9094
0