8.3.4 FP-X Thermocouple Cassette
Product No.: AFPX-TC2
Item
No. of input points
Input range
Digital value
Resolution
Sampling cycle
Total accuracy
Input impedance
Insulation
Note1) When the wire of thermocouple is broken, the digital value will change to K8000 within 70
seconds. Practice in the ladder program a process for avoiding a risk, would be resulting from a
broken wire, and exchange the thermocouple.
Note2) From the Power-on to the converted data Ready, the digital value will be K8001. Create a ladder
program not to use the data obtained during that period.
Terminal layout
Connection method
Keep the space more than 100 mm between the input line and the power line/high-voltage line.
It is recommended to ground the unit using the shielded compensating wire.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
2 channels/cassette
Thermocouple type K (-50.0 to 500.0 °C)
Thermocouple type J (-50.0 to 500.0 °C)
In normal condition: K-500 to K5000
When exceeding rated range: K-501, K5001 or K8000
When wire is broken: K8000
When data is getting ready: K8001
0.2 °C (The indication is 0.1 °C by the software averaging procedure.)
200 ms/ 2 channels
0.5% F.S. or less + Cold junction error 1.5 °C
344 kΩ
Transformer insulation, isolation IC insulation
Specifications
Thermocouple input +
CH0
+
Thermocouple input -
-
Thermocouple input +
CH1
+
Thermocouple input -
-
Used by the system.
NC
Do not connect
anything.