17.1.1 Table of System Registers for FP-X
Add-
Item
ress
Starting number setting for
5
counter
Hold type area starting number
6
setting for timer and counter
Hold type area starting number
7
setting for internal relays
Hold/
Hold type area starting number
Non-
8
setting for data registers
hold 1
Hold or non-hold setting for step
14
ladder process
Previous value is held for a
leading edge detection instruction
4
(DF instruction) with MC
Hold type area starting number for
10
PC(PLC) W0-0 link relays
Hold type area starting number for
11
Hold/
PC(PLC) W0-1 link relays
Non-
Hold type area starting number for
hold 2
12
PC(PLC) W0-0 link registers
Hold type area starting number for
13
PC(PLC) W0-1 link registers
Disable or enable setting for
20
duplicated output
Operation setting when an I/O
23
verification error occurs
Operation setting when an
26
operation error occurs
Action
on
error
Alarm battery error
(Operating setting when
4
battery error occurs)
Wait time setting for multi-frame
31
communication
Timeout setting for SEND/RECV,
32
RMRD/RMWT commands
Time
Constant value settings for scan
set-
34
time
ting
Expansion unit recognition time
36
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
1008
1008
248
C14: 12230
C30, C60:
32710
Non-hold
Hold
64
128
128
256
Disabled
Stop
Stop
Disabled
6500.0 ms
10000.0 ms
Normal
scan
0
(No wait
time)
Default
Description
value
0 to 1024
0 to 1024
0 to 256
0 to 32765
Hold/
Non-hold
Hold/
Non-hold
0 to 64
64 to 128
0 to 128
128 to 256
Disabled/Enabled
Stop/Continuation of operation
Stop/Continuation of operation
Dis-
When a battery error
abled:
occurs, a self-diagnostic
error is not issued and
the ERROR/ALARM
LED does not flash.
Ena-
When a battery error
bled:
occurs, a self-diagnostic
error is issued and the
ERROR/ALARM LED
flashes.
10 to 81900 ms
10 to 81900 ms
0: Normal scan
0 to 350 ms: Scans once each
specified time interval
0 to 10 s (0.1 second bit)
• These settings
are effective if the
optional backup
battery is
installed.
• If no backup
battery is used, do
not change the
default settings.
Otherwise proper
functioning of
hold/non-hold
values cannot be
guaranteed.