Panasonic AFPX-C30R User Manual page 141

Fp-x series
Hide thumbs Also See for AFPX-C30R:
Table of Contents

Advertisement

Communication specifications 1 Interface: RS232C, RS422, RS485
Item
Interface
Communication mode
Communication method
Synchronous method
Transmission line
Transmission distance
Note3)
Baud rate
(to be set by system register)
Computer link
Trans-
General-purpose
mission
serial communication
code
MODBUS RTU
Communication
format
(to be set by
system register)
Note4)
No. of connected units
Note1) When connecting a commercially available device that has an RS485 interface, please confirm
operation using the actual device. In some cases, the number of units, transmission distance,
and baud rate vary depending on the connected device.
Note2) The values for the transmission distance, baud rate and number of units should be within the
values noted in the graph below.
When using a baud rate of 300 bps to 38400 bps, you can set up to a maximum of 99 units
(stations) and maximum transmission distance of 1200 m.
Note3) Only 9600 bps or 19200 bps can be specified when the C-NET adapter is connected with the
RS485 interface.
Note4) The start code and end code can be used only in the general-purpose serial communication
mode.
Note5) The converter SI-35 manufactured by Lineeye Co., Ltd is recommendable for the RS485 at the
computer side. Adjust the response time for the FP-X by the SYS1 instruction if necessary.
Note6) Unit numbers should be registered by the system register.
Note7) The termination resistance of the RS485/RS422 in the COM3,COM4 and COM6 is specified by
the dip switch in the communication cassette.
There is no termination resistance at the RS232C port.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Specifications
RS232C
(non-isolated)
1:1 communication
Half-duplex communication
Start stop synchronous system
Multicore shielded line
15 m
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
Note8)
ASCII, JIS7, JIS8
ASCII, JIS7, JIS8, Binary
Binary
Data length
7 bits/8 bits
Parity
None/Even/Odd
Stop bit
1 bit/2 bits
Start code
STX/No STX
End code
CR/CR+LF/None/ETX
Note5) 6) 7)
2 units
RS422 (isolated)
RS485 (isolated)
Note1)
1:N communication
Two-wire half-duplex
communication
Shielded twisted-pair cable
or VCTF
Note1)
Max. 1200 m
Max. 1200 m
Max. 99 units
(max. 32 units when C-NET
adapter is connected.)
Note1) 2)
Note1) 2)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents