Panasonic AFPX-C30R User Manual page 331

Fp-x series
Hide thumbs Also See for AFPX-C30R:
Table of Contents

Advertisement

Target value match ON instruction (F166)
Example 1:
Example 2:
Target value match OFF instruction (F167)
Example 1:
Example 2:
FP-X Ry type – Elapsed value and target value areas of high-speed counter ch0 to chB
High-speed counter
Channel No.
ch0
ch1
ch2
ch3
ch4
ch5
ch6
ch7
ch8
ch9
chA
chB
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Control flag
Elapsed value area
R9110
DT90300 to DT90301
R9111
DT90304 to DT90305
R9112
DT90308 to DT90309
R9113
DT90312 to DT90313
R9114
DT90316 to DT90317
R9115
DT90320 to DT90321
R9116
DT90324 to DT90325
R9117
DT90328 to DT90329
R9118
DT90332 to DT90333
R9119
DT90336 to DT90337
R911A
DT90340 to DT90341
R911B
DT90344 to DT90345
If the elapsed value (DT90300 and DT90301)
for channel 0 matches K10000, output Y7 turns
on.
If the elapsed value (DT90308 and DT90309)
for channel 2 matches K20000, output Y6 turns
on.
If the elapsed value (DT90304 and DT90305)
for channel 1 matches K30000, output Y4 turns
off.
If the elapsed value (DT90312 and DT90313)
for channel 3 matches K40000, output Y5 turns
off.
Target value area
DT90302 to DT90303
DT90304 to DT90307
DT90310 to DT90311
DT90314 to DT90315
DT90318 to DT90319
DT90322 to DT90323
DT90326 to DT90327
DT90330 to DT90331
DT90334 to DT90335
DT90338 to DT90339
DT90342 to DT90343
DT90346 to DT90347

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents