0 mA to 20 mA output
Conversion characteristics graph
Table of D/A converted values
Digital input value
0
500
1000
1500
2000
2500
3000
3500
4000
When exceeding the rated range
Digital input value
Negative value
4001 or more
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Output current (mA)
0.0
2.5
5.0
7.5
10.0
12.5
15.0
17.5
20.0
Analog output value
Unchanged
(Value preceding the input of a negative value)
Unchanged
(Value preceding the input of 4001)