3.2.2 Power Supply Specifications
AC Power Supply
Item
Rated voltage
Voltage regulation range
Inrush current
Momentary power off time
Frequency
Leakage current
Internal power supply part
Guaranteed life
Fuse
Insulation system
Terminal screw
Service Power Supply for Input (Output) (AC power supply type only)
Item
Rated output voltage
Voltage regulation range
Rated output current
Overcurrent protection
Note)
function
Terminal screw
Note) This is a function to protect overcurrent temporarily. If a current load that is out of the
specifications is connected, it may lead to damages.
DC Power Supply
Item
Rated voltage
Voltage regulation range
Inrush current
Momentary power off time
Internal power supply part
Guaranteed life
Fuse
Insulation system
Terminal screw
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
100 to 240 V AC
85 to 264 V AC
40 A or less (at 240 V AC, 25 °C)
10 ms (when using 100 V AC)
50/60 Hz (47 to 63 Hz)
0.75 mA or less between input and protective earth terminals
20,000 hours (at 55 °C)
Built-in (Cannot be replaced)
Transformer insulation
M3
24 V DC
21.6 to 26.4 V DC
0.4 A
Available
M3
24 V DC
20.4 to 28.8 V DC
12 A or less (at 25 °C)
10 ms
20,000 hours (at 55 °C)
Built-in (Cannot be replaced)
Transformer insulation
M3
Specifications
E30
Specifications
E30
Specifications
E30