7.5.3 Monitoring
When using a PC(PLC) link, the operation status of the links can be monitored using the following relays.
Transmission assurance relays
For PC(PLC) link 0: R9060 to R906F (correspond to unit no. 1 to 16)
For PC(PLC) link 1: R9080 to R908F (correspond to unit no. 1 to 16)
If the transmission data from a different unit is being used with the various PLCs, check to make sure the
transmission assurance relay for the target unit is on before using the data.
Relay no.
R9060 R9061 R9062 R9063 R9064 R9065 R9066 R9067 R9068 R9069 R906A R906B R906C R906D R906E R906F
Unit no.
1
Conditions
for on/off
Operation mode relays
For PC(PLC) link 0: R9070 to R907F (correspond to unit no. 1 to 16)
For PC(PLC) link 1: R9090 to R909F (correspond to unit no. 1 to 16)
The operation modes (RUN/PROG.) can be checked for any given PLC.
Relay no.
R9070 R9071 R9072 R9073 R9074 R9075 R9076 R9077 R9078 R9079 R907A R907B R907C R907D R907E R907F
Unit no.
1
Conditions
for on/off
PLC link transmission error relay R9050
This relay goes on if a problem is detected during transmission.
Relay no.
Unit no.
1
Conditions
for on/off
Key Point: Monitoring the PC(PLC) link status
In FPWIN GR, the PC(PLC) link status items, such as the transmission cycle time and the number of
times that errors have occurred, can be monitored by selecting the PC(PLC) link switch on the FPWIN
GR Status Monitor screen.
Note:
Remote programming of the linked PLCs is not possible.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
2
3
4
5
ON: When the PLC link is normal
OFF: If transmission is stopped, a problem has occurred, or a PLC link is not used
2
3
4
5
ON: When the unit is in the RUN mode
ON: When the unit is in the PROG. mode
2
3
4
5
ON: When a transmission error has occurred in the PLC link,
or when there is an error in the setting for the PLC link area
OFF: When the unit is in the PROG. mode
6
7
8
9
10
6
7
8
9
10
R9050
6
7
8
9
10
11
12
13
14
11
12
13
14
11
12
13
14
15
16
15
16
15
16

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents