12.2.2 Master Memory Function
Overview
This function enables to transfer the data in the control unit (internal memory) such as programs to the
master memory cassette, and to copy them into another control unit (internal memory) by installing the
master memory cassette on it.
• Following data can be transferred to the master memory cassette.
1. Ladder programs
2. System registers
3. Comments
4. F-ROM data area
5. Security information (Password or uploading disabled information)
When there is no security information, no security information exists.
Change the switch on the back of the master memory cassette
The changeover switch is located at the back of the FP-X master memory cassette (AFPX-MRTC).
The default setting is "Clock/calendar only".
Transfer from the master memory to the control unit
There are two ways to transfer data.
1. Operation using the FPWIN GR
Transferring is available in the PROG mode only.
2. Automatic transfer: when the PROG mode was changed to the RUN mode
When the power supply turns on (when started in the RUN mode)
Transferring using the FPWIN GR
1. Select [Online Edit Mode] under the [Online] on the menu bar, or press the [CTRL] and [F2] keys at
the same time, to switch to the [Online] screen.
2. Select "Internal memory => Master memory" under "Tool" on the menu bar.
Internal memory  Master memory dialog box
Transferring is available in the PROG mode only.