8.3.5 FP-X RTD (Resistance Temperature Detector) Cassette
Product No.: AFPX-RTD2
Item
No. of input points
Input range
Digital conversion value
Resolution
Conversion speed
Total accuracy
Allowable input wire
resistance
Insulation
Occupation No. of I/O
contacts
Note1) Use a 3-wire type RTD.
Note2) When exceeding the rated range, reference values which are not in the range of the conversion
accuracy assurance are indicated up to ±15 °C. However, if the temperature drops (below -230
°C) or rise (over 900 °C) more, the data will be the same value (K20000) as the one at the time of
disconnection.
Note3) The digital value will be K20001 from the Power-on to the converted data Ready (approx. 3
seconds) or when an error occurs (watchdog timer time-out error) on the microcomputer for the
RTD cassette. Take care of the use of the data during this period not to influence other programs.
Note4) From the disconnection to the recovery and converted data Ready (approx. 3 seconds), the
digital value will be K20001. Take care of the use of the data during this period not to influence
other programs.
Note5) The conversion speed is 200 ms or less regardless of the number of channels to be used.
And it will be reflected in the internal data register after the completion of a scan.
Note6) The full scale (F.S.) is -200 to 850 °C for the accuracy range of RTD Pt100.
Note7) Each channel data is allocated as I/O data as the table below.
RTD cassette
Input channel
Channel 0 (CH0)
Channel 1 (CH1)
Note8) Supply power for 15 minutes or more after the power-on for performing the accurate
measurement before using the cassette.
Terminal layout
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
2 channels/cassette
Note1)
RTD Pt100
(-200.0 to +850.0 °C)
In normal condition
When exceeding rated range
When wire is broken
When data is getting ready
0.1 °C (Minimum unit)
Note5)
200 ms or less
±0.2% F.S. or less (Ambient temperature: 0 to +55°C)
Resistance value per wire: 10 Ω or less
Between analog input circuit and internal circuit: Transformer insulation,
photo coupler insulation
Between analog input channels: Transformer insulation
Note7)
Input 32 points
Expansion slot 0
(Cassette position)
WX10
WX11
Specifications
: K-2000 to K8500
: K-2150 to K-2001, K8501 to K8650
: K20000
Note3) Note4)
: K20001
Installed slot
Expansion slot 1
(Cassette position)
RTD input A
CH0
A
RTD input B
B
RTD input B
B
RTD input A
CH1
A
RTD input B
B
RTD input B
B
Do not connect anything.
NC
Note2)
Note6)
WX20
WX21