Panasonic AFPX-C30R User Manual page 466

Fp-x series
Hide thumbs Also See for AFPX-C30R:
Table of Contents

Advertisement

FP-X
Add-
Item
ress
411
Unit No. setting
Communication mode
setting
412
Selection of modem
connection
Selection of port
Communication
414
format setting
COM.
2 port
set-
ting
415
Baud rate setting
Starting address for
received buffer of
416
general (serial data)
communication mode
Buffer capacity
setting for data
417
received of general
(serial data)
communication mode
Note1) The communication format in a PC(PLC) link is fixed at the following settings:
the data length is 8 bits, odd parity, stop bit is 1.
The communication speed (baud rate) is fixed at 115200 bps.
Note2) The USB port for C30 and C60 can be selected by the system register setting.
The USB port has been selected for the COM2 port of C30 and C60 as default setting. The USB
port is 115.2 kbps despite of the baud rate setting No. 415.
The setting for No. 412 must be changed to communication cassette for using the COM2 port of
the communication cassette.
The COM2 port of the USB port and the communication cassette cannot be used at the same time.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Default
Name
value
1
Computer
link
Disabled
Built-in USB
Data length
bit: 8 bits
Parity check:
"with odd"
Stop bit: 1 bit
9600 bps
2048
2048
Description
1 to 99
Computer link
General-purpose serial communication
MODBUS RTU
Enabled/Disabled
Built-in USB
Communication cassette
Enter the settings for the various items.
Data length bit: 7 bits/8 bits
-
Parity check: none/odd/even
-
Stop bit: 1 bit/2 bits
-
The following setting is valid only when
-
the communication mode specified by
system register 412 has been set to
"General-purpose serial communication".
Terminator: CR/CR+LF/None
-
Header: STX not exist/STX exist
-
2400 bps
4800 bps
9600 bps
19200 bps
38400 bps
57600 bps
115200 bps
0 to 32764
0 to 2048