Panasonic AFPX-C30R User Manual page 185

Fp-x series
Hide thumbs Also See for AFPX-C30R:
Table of Contents

Advertisement

Link area allocation
• The link relays and link registers to be used in the PC(PLC) link are allocated in the link area of the
CPU unit. Link area allocations are specified by setting the system registers of the CPU unit.
System registers
No.
40
Range of link relays used for PC(PLC) link
41
Range of link data registers used for PC(PLC) link
42
Starting number for link relay transmission
43
Link relay transmission size
For
44
Starting number for link data register transmission
PC
45
Link data register transmission size
(PLC)
46
PC(PLC) link switch flag
link 0
47
Maximum unit number setting for MEWNET-W0
PC(PLC) link
46
PC(PLC) link switch flag
50
Range of link relays used for PC(PLC) link
51
Range of link data registers used for PC(PLC) link
For
52
Starting number for link relay transmission
PC
53
Link relay transmission size
(PLC)
54
Starting number for link data register transmission
link 1
55
Link data register transmission size
57
Maximum unit number setting for MEWNET-W0
PC(PLC) link
Note) The same maximum unit number should be specified for all the PLCs connected in the PC(PLC)
link.
Link area configuration
• Link areas consist of link relays and link registers, and are divided into areas for PC(PLC) link 0 and
PC(PLC) link 1 and used with those units.
• The link relay which can be used in an area for either PC(PLC) link 0 or PC(PLC) link 1 is maximum
1024 points (64 words), and the link register is maximum 128 words.
Note:
The PC link 1 can be used to connect with the second PC link W0 of the FP2 Multi Communication Unit
(MCU). At that time, the link relay number and link register number for the PC link can be the same
values as the FP2 (from WL64, from LD128).
Reference:
For the information on FP2-MCU, <Chapter 5 Communication Function PC(PLC) Link in FP2 Multi
Communication Unit Technical Manual ARCT1F396E>.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
Default
Set value
value
0
0 to 64 words
0
0 to 128 words
0
0 to 63
0
0 to 64 words
0
0 to 127
0
0 to 128 words
Normal
Normal: 1st half
Reverse: 2nd half
Note)
16
1 to 16
Normal
Normal: 1st half
Reverse: 2nd half
0
0 to 64 words
0
0 to 128 words
64
64 to 127
0
0 to 64 words
128
128 to 255
0
0 to 128 words
Note)
16
1 to 16

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents