Panasonic AFPX-C30R User Manual page 179

Fp-x series
Hide thumbs Also See for AFPX-C30R:
Table of Contents

Advertisement

7.4.4 1:N Communication (General-purpose Serial Communication)
Overview
The FP-X and the external units are connected using an RS485 cable. Using the protocol that matches
the external units, the F159 (MTRN) instruction is used to send and receive data.
Reference: <7.2.1 Precaution When Using RS485 Port>
System register settings
• In the default settings, the COM1 port is set to computer link mode.
Settings for COM1 port
No.
No. 412
Selection of communication mode
COM1 port
No. 413
Communication format for COM1port
No. 415
Baud rate setting for COM1port
No. 416
Starting address for receive buffer for
COM1port
No. 417
Receive buffer capacity
for COM1port
Note1) The communication format and baud rate should be set to match the connected devices.
Note2) The terminal units of AFPX-COM3, AFPX-COM4 and AFPX-COM6 are specified by the dip
switch located in the communication cassette.
Note3) The baud rates of 300, 600 and 1200 bps can be specified by the SYS1 instruction. However, the
setting value of the system register cannot be changed.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Name
Note3)
Set Value
General-purpose serial communication
Data length: ......
7 bits/8 bits
Parity check: .....
None/Odd/Even
Stop bit: ............
1 bit/2 bits
Terminator: ........
CR/CR+LF/None/ETX
Header: ............
No STX/STX
2400 to 115200 bps
DT0 to DT32764 (Initial value: DT0)
0 to 2048 words (Initial value: 2048 words)

Hide quick links: