Troubleshooting
Table 11-4
Diagnostic interrupt, continued
Byte.
Bit
0.1
Internal errors
2.4
Internal module power supply failure
(8034)
(8034)
S
Cause
S
Effect
Deactivate entire FM 353
S
Elimination
S
3.2
FEPROM errors
(8042)
(8042)
Cause
Memory for firmware code faulty
Effect
Elimination
Replace the FM 353
3.3
RAM errors
(8043)
(8043)
S
Cause
S
Effect
Elimination
Replace the FM 353
3.6
Process interrupt lost
(8046)
(8046)
S
Cause
S
Effect
S
Elimination
S
S
0.2
External errors
0.6
Module not parameterized
(8006)
(8006)
Cause
No MPI parameterization data received from the CPU
Effect
MPI interface is initialized with default values. MPI address = 12
Elimination
Check parameterization, see S7-300 description
Note: (xxxx) value = Hexadecimal notation in diagnostic buffer
11-10
Error message,
error analysis and remedy
Error response: "Everything Off", as in Table 11-2
Drastic voltage dip
FM 353 power supply faulty
Check FM 353 power connection
If FM 353 power supply defective, replace FM 353
Faulty RAM data memory
Faulty flash-EPROM data memory
A process interrupt event was detected by the FM 353 and can-
not be reported, because the same event has not yet been ac-
knowledged by the user program/CPU.
Faults on backplane bus
Incorporate OB40 into user program
Check bus connection of the module
Deactivate using MD5 process interrupt
Error response: "Everything Off", as in Table 11-2
Message/
DC5V
DIAG
DC5V
DIAG
DIAG
DC5V
DIAG
DIAG
FM 353 Stepper Drive Positioning Module
6ES7 353-1AH01-8BG0
Display
SF
SF
SF
SF
SF
SF