Programming the Technological Functions
6.8

Error list, system messages (CPU)

The Table below lists some of the errors which occur during data transfer with the
internal SFC/SFBs (RET_VAL in SFCs 51, 58 and 59 and status messages (bytes
2 and 3), SFB 52/53, system messages) (see Reference Manual System Software
for S7-300/400; System and Standard Functions).
Table 6-12
Error list
Error Code (AW-DB, DBW66)
HEX
DEC
0
0
0
8082
32898
−32638
8085
32901
−32635
80A0
32928
−32608
80A1
32929
−32607
80A2
32930
−32606
80A3
32931
−32605
80A4
32932
−32604
80A7
32935
−63601
80A9
32937
−63599
80AA
32938
−32598
to
to
to
80AF
32943
−32593
80B0
32944
−32592
80B1
32945
−32591
80B2
32946
−32590
80B3
32947
−32589
80B5
32949
−32587
80B6
32950
−32586
80C0
32960
−32576
80C1
32961
−32575
80C2
32962
−32574
80C3
32963
−32573
6-64
INT
No errors
SZL_ID invalid or not in CPU
Information currently unavailable (caused by system)
Negative acknowledgement when reading from module. Module re-
moved during Read operation or module defective.
Negative acknowledgement while writing to module. Module removed
during Write operation or module defective.
DP protocol error in layer 2 (data transfer over Profibus-DP interrupted,
e.g. due to wirebreak, missing terminator, parameterization error, etc.)
S
PROFIBUS: DP protocol error in layer 2 (data transfer over Profi-
bus-DP interrupted, e.g. due to wirebreak, missing terminator,
parameterization error, etc.)
S
PROFINET IO: General CM error
Communication problem on K bus
DP slave or module is busy
This function is not supported by DP slave or by the module.
DP slave or module is reporting a manufacturer−specific error in the
evaluation. For specifying the error, please refer to the Manufacturer
Documentation of the DP slave or of the module.
The module does not know this data record.
Invalid length specification in the RECORD parameter
The configured slot is not occupied.
Actual module type not the same as setpoint module type
DP slave or module not ready
Access to DP slave or module denied
Module does not yet have the data to be read available
Data from an identical Write job have not yet been processed on the
module
Module is currently servicing the maximum possible number of re-
quests
Needed resources (such as memory, etc.) are currently in use