3.10 Control I/O Connections

3.10 Control I/O Connections

◆ Sinking/Sourcing Mode Selection for Hardwire Baseblock Inputs

Use jumper S3 on the terminal board to select between Sink mode, Source mode or external power supply for the
HardWire Baseblock inputs H1 and H2 as shown in Table 3.15 (Default: Source mode, internal power supply.) Refer to
Switches and Jumpers on the Terminal Board on page 85
Table 3.11 Hardwire Baseblock Input Sink / Source / External Power Supply Selection
Sinking Mode
Sourcing Mode

◆ Using the Contact Outputs

The example below illustrates the use of multi-function digital outputs and the fault relay. Refer to
standard connection diagram.
86
Drive Internal Power Supply
Jumper S3
24 Vdc
HC
H1
H2
Jumper S3
24 Vdc
HC
H1
H2
Drive
Fault
Fault relay outputs and
Multi-function relay outputs
During
250 Vac 10 mA to 1A
Run
30 Vac 10 mA to 1A
(Min. load: 5 Vdc, 10 mA)
Zero
Speed
Speed
Agree 1
Figure 3.30 Contact Outputs
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
for locating jumper S3.
External
24 Vdc
External
24 Vdc
Controller
Relay
SA
MA
MB
MC
Relay
SA
M1
M2
Max
250 Vac
Relay
SA
M3
M4
Relay
SA
M5
M6
External 24 Vdc Power Supply
Jumper S3
24 Vdc
HC
H1
H2
Jumper S3
24 Vdc
HC
H1
H2
Figure 3.1
YEC_TMonly
for