Set the DIP switch S3 on the front of the drive to switch the digital input terminal logic between sinking mode and sourcing mode; the drive is preset to
sinking mode.
Set Value
SINK
SOURCE
Transistor Input Signal Using 0 V Common/Sink Mode
n
When controlling the digital inputs by NPN transistors (0 V common / sinking mode), set the DIP switch S3 to SINK and use the internal 24 V power
supply.
Transistor Input Signal Using +24 V Common/Source Mode
n
When controlling digital inputs by PNP transistors (+24 V common / sourcing mode), set the DIP switch S3 to SOURCE and use an external 24 V power
supply.
48
Table 3.11 Sinking/Sourcing Mode Setting
Figure 3.25 DIP Switch S3
SINK
Shielded cable
Forward run/stop
Reverse run/stop
SOURCE
External fault N.O.
Fault reset
Multi-speed step 1
Multi-speed step 2
Jog reference
Figure 3.26 Sinking Mode: Sequence from NPN Transistor (0 V Common)
Details
Sinking Mode (0 V common): factory setting
Sourcing Mode (+24 V common)
DIP Switch S3
SINK
SOURCE
Drive
S1
S2
S3
S4
S5
S6
S7
SINK
+24V
S3
SOURCE
SC
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)
Compact vector control drive.
200 v class, three-phase input: 0.1 to 18.5 kw.
200 v class, single-phase input: 0.1 to 4.0 kw.
400 v class, three-phase input: 0.2 to 18.5 kw (44 pages)
Compact vector control drive.
models: 200 v class, three-phase input: 0.1 to 18.5 kw;
200 v class, single-phase input: 0.1 to 3.7 kw;
400 v class, three-phase input: 0.2 to 18.5 kw (427 pages)
Ac drive-v1000
200 v class, three-phase input: 0.1 to 18.5 kw;
200 v class, single-phase input: 0.1 to 3.7 kw;
400 v class, three-phase input: 0.2 to 18.5 kw (512 pages)