Power-Up Diagnostics; Installation Procedure; Section Safety - YASKAWA SI-EP3 Technical Manual

Ac drive option. profinet
Hide thumbs Also See for SI-EP3:
Table of Contents

Advertisement

LED Name
NS (visible through drive cover)
*1
10/100
*1
LINK/ACT
*1
To verify LED states, remove the drive front cover. Do not touch the drive main circuit terminal or circuit boards when you remove
the drive front cover.

Power-Up Diagnostics

An LED test is performed each time the drive is powered up. The initial boot sequence can take several seconds.
After the LEDs complete the diagnostic LED sequence, the option is successfully initialized. The LEDs then
assume operational conditions as shown in
Sequence
1
2
3
4
5
6
5

Installation Procedure

Section Safety

DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before
servicing, disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal
capacitor stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage
decreases below 50 Vdc. When all indicators are OFF, measure for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.
WARNING
Electrical Shock Hazard. Do not operate the drive when covers are missing. Replace covers and shields
before you operate the drive. Use the drive only as specified by the instructions. Some figures in this section include drives
without covers or safety shields to more clearly show the inside of the drive. If covers or safety shields are missing from the
drive, it can cause serious injury or death.
WARNING
Electrical Shock Hazard. Only let approved personnel install, wire, maintain, examine, replace parts, and
repair the drive. If personnel are not approved, it can cause serious injury or death.
WARNING
Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. If you
touch the internal components of an energized drive, it can cause serious injury or death.
YASKAWA SIEP C730600 89E PROFINET Technical Manual
Indication
Color
Status
Red
Flashing (4)
Green/Red
Flashing
-
OFF
Green
ON
Green
Flashing
Red
ON
Red
Flashing (1)
Red
Flashing (2)
Red
Flashing (3)
Yellow
OFF
Yellow
ON
Green
OFF
Green
ON
Green
Flashing
Table
4.3.
Table 4.3 Power-Up Diagnostic LED Sequence
Module Status (MS)
Green
Red
Green
Green
Green
Green
Operating Status
Init failure (non-fatal)
Option self-test
Offline or Power supply OFF
Connected
Connected and stopped
bUS fault
Lost communication
Lost link
IP address settings bad
10 Mbps is established
100 Mbps is established
Link is not established
Link is established
Link is established and there is network
activity
Network Status (NS)
OFF
OFF
OFF
Green
Red
OFF
5 Installation Procedure
Description
Failed to initialize module.
The option is in self-test mode.
-
Connection established with I/O controller
and in RUN mode.
Connection established with I/O controller
and in STOP mode.
Unrecoverable bUS fault.
Host communication is temporarily lost.
No link detected to network.
Use the operator or DriveWizard to check
and change F7 parameters, then cycle
power. You can also set the PLC to assign
the IP address.
This will clear the fault automatically.
-