2: P
S
RODUCT
PECIFICATIONS
■ Output Specifications
Type No.
Output Points
COM1
per Common
COM2
Line
Output Type
1
Load Current
1 Common
Minimum Switching Load
Initial Contact Resistance
Electrical Life
Mechanical Life
Rated Load
Between Output
Terminal and FG
Between Output
Withstand
Terminal and Internal
Voltage
Circuit
Between Output
Terminals (COMs)
Output Delay
ON
Input to Relay
OFF
ON
Output Relay Status
OFF
2-60
4
1a contact
2 A maximum
7 A maximum
1.0 mA/5.0V DC (reference value)
30 mΩ or lower
100,000 operations minimum (rated load 1,800 operations/hour)
20,000,000 operations minimum (no load 18,000 operations/hour)
240V AC 2 A (resistive load, cosφ=0.4 inductive load)
30V DC 2 A (resistive load, L/R=7 ms inductive load)
2,300V AC 1 minute
2,300V AC 1 minute
2,300V AC 1 minute
FC6A S
M
S
A
ERIES
ICRO
MART
LL
FC6A-M08BR1
OFF Bounce:
6 ms maximum
OFF Delay:
10 ms maximum
ON Bounce:
6 ms maximum
ON Delay:
6 ms maximum
-
-O
T
U
'
M
IN
NE
YPE
SER
S
ANUAL
FC6A-M24BR1
4
4
FC9Y-B1722