iDect FC6A series User Manual page 365

Microsmart all-in-one type
Table of Contents

Advertisement

(2) Signal Type
The signal type that can be set differs according to the analog cartridge model. Select the analog cartridge that corresponds to
the user application and set the signal type.
For details on signal type, see "Analog Cartridge Specifications" on page 10-2.
(3) Data Type
The analog value can be handled in the range of the specified data type (minimum value to maximum value). The data types are
as follows.
Data Type
Binary data
The analog value can be stored in the range of 0 to 4,095.
The analog value can be stored in the range of minimum value to maximum value. The minimum and maximum
Optional range
values can be set in the range of -32,768 to 32,767. For the minimum and maximum values, see "(4) Minimum,
maximum values of analog value linear conversion" on page 10-5.
Celsius
The analog value can be stored in the linear conversion range of the temperature sensor set as the data type.
For details, see the analog input value linear conversion range when set to Celsius or Fahrenheit.
Fahrenheit
(4) Minimum, maximum values of analog value linear conversion
When Data Type is set to "Optional range", these values set the minimum and maximum when performing a linear conversion
of the analog value. The minimum and maximum values can be set to any value in the range of -32,768 to 32,767. However, the
minimum value must be set to a value smaller than the maximum value.
(4) Linear conversion range of analog input value when set to Celsius or Fahrenheit
When the data type is set to Celsius or Fahrenheit, the analog input value is linearly converted in the range of the following
table.
Signal Type
Type K thermocouple
Type J thermocouple
Type R thermocouple
Type S thermocouple
Type B thermocouple
Type E thermocouple
Type T thermocouple
Type N thermocouple
Type C thermocouple
Pt100
Pt1000
Ni100
Ni1000
Celsius
Temperature (0.1°C)
-200.0 to 1,300.0
-2,000 to 13,000
-200.0 to 1,000.0
-2,000 to 10,000
0.0 to 1,760.0
0 to 17,600
0.0 to 1,760.0
0 to 17,600
0.0 to 1,820.0
0 to 18,200
-200.0 to 800.0
-2,000 to 8,000
-200.0 to 400.0
-2,000 to 4,000
-200.0 to 1,300.0
-2,000 to 13,000
0.0 to 2,315.0
0 to 23,150
-200.0 to 850.0
-2,000 to 8,500
-200.0 to 600.0
-2,000 to 6,000
-60.0 to 180.0
-600 to 1,800
-60.0 to 180.0
-600 to 1,800
FC6A S
M
S
A
ERIES
ICRO
MART
Description
Analog Input Value
Temperature (0.1°F)
328.0 to 2,3720.0
328.0 to 1,832.0
32.0 to 3,200.0
32.0 to 3,200.0
32.0 to 3,308.0
328.0 to 1,472.0
328.0 to 752.0
328.0 to 2,372.0
32.0 to 4,199.0
328.0 to 1,562.0
28.0 to 1,112.0
76.0 to 356.0
76.0 to 356.0
-
-O
T
U
'
M
LL
IN
NE
YPE
SER
S
ANUAL
10: A
NALOG
Fahrenheit
Analog input value
-3,280 to 23,720
-3,280 to 18,320
320 to 32,000
320 to 32,000
320 to 33,080
-3,280 to 14,720
-3,280 to 7,520
-3,280 to 23,720
320 to 41,990
-3,280 to 15,620
-3,280 to 11,120
-760 to 3,560
-760 to 3,560
FC9Y-B1722
C
ARTRIDGE
10-5