iDect FC6A series User Manual page 117

Microsmart all-in-one type
Table of Contents

Advertisement

(9) Dummy Cartridge
A removable dummy cartridge that protects the cartridge slot. Remove the dummy cartridge when connecting an analog
cartridge.
(10) HMI-Ethernet Port
This port allows Ethernet communication with connected devices that are equipped with an Ethernet interface.
Function Specifications
Type No.
Rated Power Voltage (Supplied from
Module)
HMI-Ethernet Port
Connector
Insertion/Removal
Durability
Module
5V DC
Internal Current
24V DC
Draw
Ground
Ground Wire
Weight
■ HMI-Ethernet Port Specifications
Points
Communication Type
Communication Speed
Communication Functions
Connector
Cable
Maximum Cable Length
Isolation between Internal Circuit
■ Ethernet Communication Specifications
Number of Connections
Communication Mode
Web Server Function
Web Data Storage
Web Data Capacity
Send E-mail Function
■ LCD Specifications
Type
Resolution
Number of Characters
Display Content
Contrast Adjustment
Backlight
5V DC
24V DC
RJ45
100 times minimum
300 mA
15 mA
D-type ground (Type 3 ground)
UL1007 AWG18
170 g
1
IEEE 802.3 compliant
10BASE-T, 100BASE-TX
Maintenance communication
RJ45 (Auto MDI/MDI-X compatible)
CAT 5. STP or higher
100 m
Pulse transformer isolated
8 maximum
Maintenance Communication
Yes
FROM
5 Mbyte (Total size of the system web page and user web page)
Yes
STN monochrome LCD
64 x 192 pixels
24 digits x 8 lines (8 x 8 pixel font)
12 digits x 8 lines (16 x 8 pixel font)
12 digits x 4 lines (16 x 16 pixel font)
System menus, messages, operation status monitor
Not possible
Yes (can be turned on and off)
FC6A S
M
S
A
ERIES
ICRO
MART
FC6A-PH1
-
-O
T
U
'
M
LL
IN
NE
YPE
SER
S
ANUAL
2: P
S
RODUCT
PECIFICATIONS
FC9Y-B1722
2-89