iDect FC6A series User Manual page 348

Microsmart all-in-one type
Table of Contents

Advertisement

9: F
M
UNCTIONAL
ODULES
(8) Status
The status of the analog input data (7) is stored in data registers.
Status
0
1
2
3
4
5
6
7
8
9
10 to 65,535
*1 When the analog input value is the upper limit value in the below table or higher, the out of maximum range error occurs. When the analog
input value is the lower limit value in the below table or lower, the out of minimum range error occurs.
Signal Type
0 to 10 V
-10 to +10 V
0 to 20 mA
4 to 20 mA
Type K thermocouple
Type J thermocouple
Type R thermocouple
Type S thermocouple
Type B thermocouple
Type E thermocouple
Type T thermocouple
Type N thermocouple
Type C thermocouple
Pt100
Pt1000
NI100
NI1000
NTC thermistor
PTC thermistor
PTC thermistor (threshold)
Resistance measurement
Expansion 0 to 20 mA
Expansion 4 to 20 mA
*2 Expansion 0 to 20 mA or expansion 4 to 20 mA only
*3 Expansion 4 to 20 mA only
9-8
Operating normally
Converting data
Initializing
Parameter setting error
Hardware fault (external power supply error)
Wiring fault (out of maximum range)
Wiring fault (out of minimum range)
Reserved
When the analog input value is greater than 20 mA and less than the upper limit value
When the analog input value is greater than the lower limit value and less than 4 mA
Reserved
-0.2 V
-10.4 V
-0.4 mA
3.68 mA
-200.0°C
-200.0°C
0.0°C
0.0°C
0.0°C
-200.0°C
-200.0°C
-200.0°C
0.0°C
-200.0°C
-200.0°C
-60.0°C
-60.0°C
100 Ω
-90.0°C/100 Ω
100 Ω
100 Ω
-0.4 mA
1.20 mA
FC6A S
M
S
A
ERIES
ICRO
MART
Description
*1
*1
Lower Limit Value
-
-O
T
U
'
M
LL
IN
NE
YPE
SER
S
ANUAL
*2
*3
Upper Limit Value
10.2 V
10.4 V
20.4 mA
20.32 mA
1,300.0°C
1,000.0°C
1,760.0°C
1,760.0°C
1,820.0°C
800.0°C
400.0°C
1,300.0°C
2,315.0°C
850.0°C
600.0°C
180.0°C
180.0°C
200 kΩ
150.0°C/10 kΩ
10 kΩ
32 kΩ
23.54 mA
23.17 mA
FC9Y-B1722