Wiring Arrangement and Wiring Examples
Do not connect a thermocouple to a part with hazardous voltage (60V DC or peak 42.4V DC or higher part).
•
Caution
Before turning on the power, please check that the wiring is correct. If the wiring is incorrect, the analog cartridge may
•
be damaged. When the analog cartridge may malfunction due to noise, wire it with a shielded cable and connect both
ends to the FG.
When connecting cables to the analog cartridges, the tightening torque is 0.22 to 0.25 Nm.
•
FC6A-PK2AV
OUT0
+
–
NC
+
–
0 to 10 V
Analog Voltage Input Device
FC6A-PJ2A
IN0
+
–
+
+
–
0 to 10 V
Analog Current Output Device
OUT1
+
–
NC
+
–
0 to 10 V
Analog Voltage Input Device
IN1
+
–
+
–
+
0 to 20 mA
4 to 20 mA
Analog Current Output Device
FC6A S
M
S
A
ERIES
ICRO
MART
FC6A-PK2AW
OUT0
NC
–
+
–
4 to 20 mA
Analog Voltage Input Device
FC6A-PJ2CP
IN0
A
B
B'
+
–
NC
A
B
B'
Pt / Ni
Resistance Thermometer
-
-O
T
U
'
M
LL
IN
NE
YPE
SER
S
ANUAL
2: P
RODUCT
OUT1
NC
–
+
–
4 to 20 mA
Analog Voltage Input Device
IN1
A
B
+
–
+
–
Thermocouple
FC9Y-B1722
S
PECIFICATIONS
+
+
B'
NC
2-93