When Run/Stop PLC by Function Switch and Turn on M8000 when function switch is changed from "0" to "1". are
enabled (For the default setting)
RUN/STOP status
(When RUN/STOP control setting disabled)
Function switch status
(1) When the function switch is 0, the FC6A Series MicroSmart remains in the stopped state, even when M8000 is turned on.
(2) When the function switch is changed from 0 to 1, and when M8000 is off, it is turned on (remains on when on) and the FC6A
Series MicroSmart runs.
(3) When the function switch is 1, the FC6A Series MicroSmart stops when M8000 is turned off.
(4) When the function switch is changed from 1 to 0, the FC6A Series MicroSmart stops.
*
M8073 turns on and off according to the status of the function switch.
WindLDR Settings
When assigning the function to control FC6A Series MicroSmart running and stopping to the function switch, you must configure
Run/Stop Control under Function Switch in the WindLDR Function Area Settings.
Operation procedure
From the WindLDR menu bar, select Configuration > Run/Stop Control.
1.
The Function Area Settings dialog box is displayed.
Select the Run/Stop PLC by Function Switch check box.
2.
Select the Turn on M8000 when function switch is changed from "0" to "1". check box.
Click OK.
3.
This concludes configuring the settings.
5-10
(1)
RUN
STOP
ON
Start control
(M8000)
OFF
1
Function switch
0
ON
(M8073)
OFF
FC6A S
M
S
ERIES
ICRO
MART
(2)
(3)
(1)
A
-
-O
T
U
'
M
LL
IN
NE
YPE
SER
S
ANUAL
(2)
(4)
FC9Y-B1722

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents