iDect FC6A series User Manual page 439

Microsmart all-in-one type
Table of Contents

Advertisement

Troubleshooting Diagram 6
Cannot stop or reset operation.
Is stop or
reset input designated in
the WindLDR Function Area
Settings?
Is the designated stop or
reset input on?
Monitor the designated stop or reset
input using WindLDR on a computer.
Does the monitored input
turn on and off?
Call IDEC for assistance.
Note: To turn off M8000, enter 0 in the Current Value box in the Custom Monitor dialog box.
For details on special internal relay M8000, see "M8000: Start Control" on page 6-7.
NO
YES
NO
YES
NO
YES
FC6A S
M
S
ERIES
ICRO
MART
Note: To monitor M8000, from the WindLDR menu bar, select
Online > Monitor > Monitor, then Online > Custom > New
Custom Monitor. Enter M8000 in the Device box in the Custom
Monitor dialog box.
Turn on the designated input.
The input circuit in the FC6A Series
MicroSmart is damaged.
Replace the FC6A Series MicroSmart.
A
-
-O
T
U
'
M
LL
IN
NE
YPE
SER
S
ANUAL
13: T
ROUBLESHOOTING
Monitor the start control special internal
relay M8000 using WindLDR on a
computer.
YES
Is M8000 off?
NO
Turn off the start control special internal
relay M8000 using WindLDR on a
computer.
FC9Y-B1722
13-13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents