iDect FC6A series User Manual page 36

Microsmart all-in-one type
Table of Contents

Advertisement

2: P
S
RODUCT
PECIFICATIONS
Power Supply Specifications
■ AC Power Type
Type No.
Rated Operating Voltage
Voltage Fluctuation Range
Rated Power Frequency
Maximum Power Consumption
FC6A-C16R1AE
FC6A-C24R1AE
FC6A-C40R1AE
FC6A-C40R1AEJ
Allowable Momentary Power
Interruption
Withstand Voltage
Insulation Resistance
Inrush Current
Isolation
Ground
Grounding Wire
Power Supply Wire
Effect of Improper Power Supply
Connection
FC6A-C16R1AE
FC6A-C24R1AE
Weight
FC6A-C40R1AE
FC6A-C40R1AEJ
2-8
FC6A-C16R1AE, FC6A-C24R1AE, FC6A-C40R1AE, FC6A-C40R1AEJ
100 to 240V AC
85 to 264V AC
50/60 Hz (47 to 63 Hz)
33 VA
35 VA
41 VA
37 VA
10 ms or longer (when rated power supply voltage)
Between power and PE terminals: 1,500V AC, 1 minute
Between input and PE terminals: 1,500V AC, 1 minute
Between relay output and PE terminals: 2,300V AC, 1 minute
Between power and input terminals: 1,500V AC, 1 minute
Between power and relay output terminals: 2,300V AC, 1 minute
Between input and relay output terminals: 2,300V AC, 1 minute
Between power and PE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between input and PE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between relay output and PE terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between power and input terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between power and relay output terminals: 100 MΩ or higher (500V DC insulation resistance tester)
Between input and relay output terminals: 100 MΩ or higher (500V DC insulation resistance tester)
40 A maximum
Between power terminal and internal circuit: Transformer isolated
D-type ground (Class 3 ground)
See "Recommended Ferrule List" on page 3-35
See "Recommended Ferrule List" on page 3-35
Reverse polarity: Normal operation
Improper voltage or frequency: Permanent damage may be caused
Improper lead connection: Permanent damage may be caused
370 g
420 g
560 g
560 g
FC6A S
M
S
A
ERIES
ICRO
MART
LL
Standalone
-
-O
T
U
'
M
IN
NE
YPE
SER
S
ANUAL
When Maximum Load is Connected
54 VA
61 VA
74 VA
74 VA
FC9Y-B1722