iDect FC6A series User Manual page 346

Microsmart all-in-one type
Table of Contents

Advertisement

9: F
M
UNCTIONAL
ODULES
(4) Filter
The analog input is filtered so it reaches approximately 99% of the analog input in the set time. Rapid fluctuations in the analog
input can be reduced by setting the filter, but increasing the filter slows down the tracking of fluctuations in the analog input.
The filter must be set for each channel.
Input filter example
100
90
80
70
60
50
40
30
20
10
0
-20
0
Filter (ms)
0
50 to 50,000
9-6
Filter: 100 ms
20
40
60
Elapsed time (ms)
The value is not filtered.
The analog input filter can be set in 50 ms increments.
The analog input is filtered so that approximately 99% of the analog input is reached in the specified filter.
FC6A S
M
S
ERIES
ICRO
MART
Reaches approximately 99% of the analog
input in the set filter (100 ms).