Program
M8120 (initialize pulse) is a special internal relay that turns on when the FC6A Series MicroSmart runs.
M8120
M0000
M8120
5-28
MOV(D)
S1-
D1-
REP
1000
D0004
MOV(D)
S1-
D1-
REP
0
D8216
MOV(W)
S1-
D1-
REP
1
D0002
M8031
M0000
M8031
M0000
M8032
FC6A S
M
S
ERIES
ICRO
MART
1st scan
Store 1,000 in preset value 1 (D0004, D0005)
Store the reset value in D8216, D8217
Store 1 in the next preset value number (D0002)
Turn off gate input (M8031)
Turn off M0000
3rd scan
Detect the rising edge of M0000, turn on gate input (M8031)
Start high-speed counter counting in the END processing
after the 3rd scan is executed
2nd scan
Detect the falling edge of the initialize pulse, M0000 and M8032 turn on
Initialize the current value with the reset value in the END processing
after the 2nd scan is executed
M8032 (reset input) is a special internal relay that stores the preset
value (D8216, D8217) in the current value (D8210, D8211).
A
-
-O
T
U
'
M
LL
IN
NE
YPE
SER
S
ANUAL
FC9Y-B1722