iDect FC6A series User Manual page 120

Microsmart all-in-one type
Table of Contents

Advertisement

2: P
S
RODUCT
PECIFICATIONS
Type No.
Input Type
Maximum Error at
25°C
Input Error
Temperature
Coefficient
Digital Resolution
Data
Input Value per Step
Application Data Type
Monotonicity
Input Data Out of
Range
Maximum Temporary
Deviation
during Electrical
Noise
Noise Tests
Resistance
Recommended Cable
Crosstalk
Isolation
Effect of Improper Input Connection No damage
Maximum Permanent Allowed
*4
Overload
(No Damage)
Selection of Input Type and Input
Range
Calibration or Verification to
Maintain Rated Accuracy
*1 Total input delay time indicates the total value of the sample repetition time plus the internal processing time. The total input delay time
increases in proportion to the number of channels used.
*2 The arbitrary setting is a function that uses the digital resolution data by scaling it to arbitrary data (that arbitrarily sets the lower limit value and
the upper limit value). The range setting (-32,768 to 32,767) is specified with data registers.
Example: When -5 V is input, 1,024 is displayed as long as the arbitrary setting is not configured, but -500 is displayed when the arbitrary setting is
configured as upper limit value = 1,000 and lower limit value = -1,000, and this makes it easier to intuitively read the input voltage value.
When the digital resolution data is 12 bits
Lower Limit Value
0
*3 Input data out of range is reflected in the status of the analog module.
*4 The maximum voltage/current value that can be input without damage.
2-92
FC6A-PJ2A
Voltage
±0.1% of full scale
±0.02% of full scale/°C
4,096 steps (12 bits)
4.88 µA
2.44 mV
(0 to 20mA DC)
(0 to 10V DC)
3.91 µA
(4 to 20mA DC)
Can be arbitrarily set for each channel in a range between -32,768 to 32,773
Yes
*3
Detectable
Max ±4.0% of full scale
Pair shielded cable
Max 1 LSB
None
13 V
40 mA
Using programming software
Not possible
Upper Limit Value
4,095
FC6A S
M
S
A
ERIES
ICRO
MART
LL
Current
Resistance Thermometer
±0.1% of full scale
±0.02% of full scale/°C
Pt100: Approx. 10,500
(equivalent to 14 bits)
Pt1000: Approx. 8,000
(equivalent to 13 bits)
Ni100: Approx. 2,400
(equivalent to 12 bits)
Ni1000: Approx. 2,400
(equivalent to 12 bits)
0.1°C
0.18°F
Pair cable
13 V
-
-O
T
U
'
M
IN
NE
YPE
SER
S
ANUAL
FC6A-PJ2CP
Thermocouple
±0.1% of full scale
Cold junction compensation
accuracy ±4.0°C or lower
Exceptions
R, S thermocouple error:
±6.0°C
(0 to 200°C range only)
B thermocouple error:
Not guaranteed
(0 to 300°C range only)
K, J, E, T, N thermocouple error:
±0.4% of full scale
(0°C or lower range only)
K: 15,000 (14 bits)
J: 12,000 (14 bits)
R: 17,600 (15 bits)
S: 17,600 (15 bits)
B: 18,200 (15 bits)
E: 10,000 (14 bits)
T: 6,000 (13 bits)
N: 15,000 (14 bits)
C: 23,150 (15 bits)
0.1°C
0.18°F
*2
FC9Y-B1722