(6) Status
The analog status shows the status of the analog input or analog output for each channel. If the status is 0, this means the
value is normal as an analog value.
Analog input
Status
0
Operating normally
Converting data (occurs for approximately 500 ms after the power is turned on and after the
1
program is downloaded)
2
Initializing
3 to 4
Reserved
Wiring fault (out of maximum range)
5
Signal type
Wiring fault (out of minimum range, open current loop)
6
Signal type
7
Reserved (analog cartridge correction value error)
There is a difference in the configured content for the installed analog cartridge and the user
8
program
9
The analog cartridge has not been installed
10
The analog cartridge has been installed, but the type has been set to unused
11 to 65,535 Reserved
*1 The analog cartridge version number is printed on the side of the analog cartridge. For details, see "Checking the Version Number" on page
10-2.
Analog output
Status
0
Operating normally
1
Reserved
2
Initializing
3
Parameter setting error
4 to 7
Reserved
There is a difference in the configured content for the installed
8
analog cartridge and the user program
9
The analog cartridge has not been installed
The analog cartridge has been installed, but the type has been set
10
to unused
11 to 65,535 Reserved
Description
Voltage
0 to 10 V
4 to 20 mA
Current
0 to 20 mA
Thermocouple/
Upper limit value or higher
resistance thermometer
Voltage
0 to 10 V
4 to 20 mA
Current
0 to 20 mA
Thermocouple/
Lower limit value or higher
resistance thermometer
Description
FC6A S
M
S
A
ERIES
ICRO
MART
*1
For V100
: 10.0 V or higher
*1
For V201
and later: 10.2 V or higher
*1
For V100
: 20.0 mA or higher
*1
For V201
and later: 20.32 mA or higher
*1
For V100
: 20.0 mA or higher
*1
For V201
and later: 20.4 mA or higher
*1
For V100
: 0 V or lower
*1
For V201
and later: -0.2 V or lower
*1
For V100
: 4.0 mA or lower
*1
For V201
and later: 3.68 mA or lower
*1
For V100
: 0 mA or lower
*1
For V201
and later: -0 mA or lower
Current analog output value
0 V / 4 mA
Analog output value immediately before the error occurred
0 V / 4 mA
0 V / 4 mA
-
-O
T
U
'
M
LL
IN
NE
YPE
SER
S
ANUAL
10: A
NALOG
Analog Input Value
Current analog input value
Undefined
0
Upper limit value
Lower limit value
Undefined
Undefined
Undefined
Analog Output Signal
FC9Y-B1722
C
ARTRIDGE
10-7