Graphic Operation Terminal F940GOT
• This window is displayed in the screen mode (while a user screen is displayed).
When the display is changed over to a system screen (the alarm mode), the window disap-
pears. However, if an alarm device is ON, the window is displayed again when the display is
changed over to a user screen (the screen mode) again.
In the case of SWoD5C-GOTR-PACK
By setting "Detail Display Destination" in "Basic Setting" in "Alarm History Common Setting" in
the software to "Comment Window", detailed comment messages corresponding to alarm
devices can be displayed.
In this case, the object "Alarm History" or "Alarm List" is displayed on the user screen, and
detailed comment messages are displayed when a touch key whose key code has been set to
"FFB8 (detail display)" is pressed.
Alarm history display : Refer to Paragraph 12.3.5.
Alarm list display
2) Screen changeover (changeover of base screen)
If "screen changeover" is selected, when a specified alarm device becomes ON from OFF, a
user screen displayed at that time in the screen mode is changed over to a screen of speci-
fied No. (When the SWoD5C-GOTRE-PACK is used, a screen of specified No. is displayed
when the DETAIL key is pressed.)
The display can be returned from the specified screen to the previous screen using the fol-
lowing procedure.
• In the case of the FX-PCS-DU/WIN-E
Set "Destination Screen" to "DU memory" in the "Change Screen" object of the changed-
over screen.
• In the case of the SWoD5C-GOTRE-PACK
Set "Destination Screen" to "Upper Hierarchy" in "Change Screen" of the changed-over
base screen.
3) Printing
When an alarm has occurred, the date of occurrence and a corresponding alarm message
can be printed.
Alarm messages should have been entered in half-width characters. The communication
condition of the used printer should have been set in "SERIAL PORT" in "SET-UP MODE" in
the GOT.
: Refer to Paragraph 12.3.6.